AGASTAT Industrial Partner

7012ND - Agastat 7012ND Industrial Electropneumatic Timing Relay | On-delay Operation |...

larger image

Request Quote
For Price
Part Number:
7012ND
Model Number:
7012ND
Make:
AGASTAT
Lead Time:
Available
Qty In Stock:
Available

Agastat 7012ND Industrial Electropneumatic Timing Relay | On-delay Operation | 2PDT (2 form C) Contact Arrangement | 48VDC Coil Voltage | 5 to 50 Seconds Timing Range Simple Type: Electropneumatic Timing Relay

There are three main components of Series 7000 Timing Relays: Calibrated Timing Head uses no needle valve, recirculates air under controlled pressure through a variable orifice to provide linearly adjustable timing. Patented design provides instant recycling, easy adjustment and long service life under severe operating conditions. Precision-Wound Potted Coil module supplies the initial motive force with minimum current drain. Total sealing without external leads eliminates moisture problems, gives maximum insulation value. Snap-Action Switch Assembly - custom-designed over-center mechanism provides greater contact pressure up to transfer time for positive, no flutter action. Standard switches are DPDT arrangement, with flexible beryllium copper blades and silver-cadmium oxide contacts. Special "timing-duty" design assures positive wiping action, sustained contact pressure and greater heat dissipation during long delay periods. Each of these sub-assemblies forms a self-contained module which is then assembled at the factory with the other two to afford a wide choice of operating types, coil voltages, and timing ranges.

Download the datasheet (PDF)

For Resellers and High Volume Orders:
Please request a quote to obtain preferred pricing.

Features

  • Auxiliary timed and instantaneous switches can be added for greater switching flexibility
  • Available in 2-pole or 4-pole models
  • Available in on-delay, true off-delay, and on/off-delay
  • Easy-to-reach screw terminals, all on the face of the unit, clearly identified
  • Inherent transient immunity
  • Many mounting options: Surface mount, Panel mount, Octal plug-in mounting
  • Modular assembly - timing head, coil assembly and switch-block are all individual modules, with switches field-replaceable
  • Numerous enclosure options: explosion proof, dust tight, watertight, hermetically-sealed, NEMA 1
  • Options: quick-connect terminals, dial stops, and transient protection module
  • Oversize time-calibrated adjustment knobs, serrated with high-resolution markings visible from all angles makes the timer easy to set timers
  • Standard voltages from 6-550VAC and 12-550VDC (special voltages available)
  • Timing from 0.1 seconds to 60 minutes, in linear increments

Specifications

    General
  • Dielectric: Withstands 1500 volts RMS 60Hz between terminals and ground
  • Insulation Resistance: 500 Megohms with 500VDC applied.
  • Mounting/Terminals: Normal mounting of the basic unit is in a vertical position, from the back of the panel.
  • Operating Modes: On-delay (delay on pick-up)
  • Operating Temperature: -22°F to +167°F (-30°C to + 75°C)
  • Power Consumption: Approximately 8 watts power at rated voltage
  • Relay Operate Time: 50 msec. for off-delay models
  • Relay Release Time: 50 msec. for on-delay models
  • Reset Time: 50 msec
  • Storage Temperature: -40°F to +167°F (-40°C to +75°C)
  • Surge Life: Applied 100,000 times continuously with the interval of 10 seconds at room temperature. Below 68 VAC: 12A; Above 68 VAC: 35A
  • Timing Adjustment: Timing is set by simply turning the dial to the desired time value

 

Applications

  • None Available

Aliases